CISA flags denial-of-service flaws in Siemens building automation controllers
CISA's advisory covers multiple remotely exploitable vulnerabilities in widely deployed Siemens building automation controllers used across critical manufacturing, energy, healthcare, financial services and government facilities worldwide. Compliance and OT security teams running APOGEE, TALON or Desigo PXC/PXM equipment should check which product lines have patches available versus those left on mitigation-only guidance.
- CISA released advisory ICSA-26-295-08 on October 22, 2026 covering Siemens APOGEE, TALON and Desigo PXC/PXM products.
- The highest-rated vulnerability, affecting APOGEE MBC (PPC) BACnet, carries a CVSS v3 base score of 8.2 across three CWE categories: out-of-bounds read, integer underflow and stack-based buffer overflow.
- Siemens has issued vendor fixes for APOGEE PXC Compact/Modular and TALON TC Compact/Modular, updating to V3.5.7 (BACnet) or V2.8.21 (P2 Ethernet).
- Siemens states no fix is planned for APOGEE MBC/MEC (PPC) variants or any of the thirteen listed Desigo PXC/PXM controller models.
- Recommended mitigations for unpatched products include network segmentation behind gateways/firewalls and disabling the FTP/Web service, which Siemens says is off by default.